Questions Asked in 2024-25
Power System Ii (BEE601) — complete question paper · 70 marks · 3 Hours
Section AAttempt all questions in brief. 02 x 7 = 14
- aDuring three phase fault which sequence component should be ca lculated? Explain with the reason
- bExplain the need of load flow analysis
- cEnumerate different types of buses and their significance in p ower system
- dA 100 kV surge travels on an overhead line with a surge impeda nce of 500 Ω, which is terminated by a cable with a surge impedance of 50 Ω. Calculate the magnitude of the reflected and transmitted voltage?
- eEnumerate five factors affecting the transient stability of po wer system
- fClassify relays based on their application
- gDifferentiate between restriking and recovery voltage
Section BAttempt any three of the following: 07 x 3 = 21
- aA synchronous generator feeds bus 1 of a system. A power net work feeds bus 2 of the system. Buses 1 and 2 are connected through a transformer and a transmission line. Per unit reactances of the various components are: Generator (connected to bus bar 1): 0.25 Transformer: 0.12 Transmission Line 0.28 The power network can be represented by a generator with a reac tance (unknown) in series. With the generator on no load and with 1.0 pu voltage a t each bus under operating condition, a three-phase short circuit occurring on bus 1causes a current of 5.0pu to flow into the fault. Determine the equivalent reactance of the power network
- bExplain 𝑍ௌ building algorithms with all types of modification
- cExplain Bewley’s Lattice diagram. Prove the statement that a n open circuited line behaves as a leading power factor network
- dDerive power flow equations and prove that the reactive powe r flow in the transmission line is proportional to the difference between magnitudes of se nding end and receiving end voltages
- eExplain the working of overcurrent relay through neat diagra m
Section CAttempt any one part of the following: 07 x 1 = 07
- aDerive the expression for fault current of double line to gr ound fault and draw the related sequence networks
- bDesign the positive, negative and zero sequence network of t he system shown in mentioned figure when a single line to ground fault (on phase a ) occurs on bus 1. Also calculate the fault current. The rating of the machines are 1200KVA, 600V with X՛ =X 2= 10%, X 0=5%. T1 is rated 1200KVA, 600V/3300V with leakage reactance of 5%, T 2 is rated 1200KVA, 3300V/600V with leakage reactance of 5%. The reactance of the t ransmission line are X1= X2=20% and X0=40% on the base of 1200KVA, 3300V. The reactance of the neutra l grounding reactors are 5% on the KVA and voltage base of the machine
- aThe one line diagram of a simple four bus system is shown in mentioned figure. The line impedances are mentioned in the table. The shunt admittances at a l l t h e b u s e s a r e assumed to be negligible. (a) Find 𝑌ௌ if the line shown dotted is not connected. (b) What modifications need to be carried out in 𝑌ௌ if the line shown dotted is connected. Line, bus to bus R, pu X, pu
- bExplain the application of Newton- Raphson method for load f low studies. Enumerate its advantages/disadvantages over Gauss-Siedel method
- aA transmission line has an inductance of 16mH and a capacita nce of 0.1µf is connected to
- acable which is having an inductance of 1.6H and a capacitance of 1mf. If a surge of 40kV is transmitted from transmission line towards the cable. Find: i. Transmitted voltage wave in cable ii. Transmitted current wave in cable iii. Reflected voltage and current waves iv. Incident current wave
- bExplain the concept of Surge Impedance Loading (SIL). Calcul ate the expression for maximum power during SIL. Write advantages of SIL
- aExplain equal area criteria to study transient stability. El aborate the stability when mechanical input suddenly changed with the help of equal area criteria
- bDerive the expression for effect of clearing time on stabili ty
- aExplain arc production, arc quenching/extinction and its met hods in circuit breaker
- bExplain following in detail: i. Fault clearing time ii. Relay time iii. Breaker time iv. Overreach v. Underreach
Question text is extracted from the official AKTU question paper PDF above. Hindi translations are omitted — every question is printed in English in the original paper. Last verified: 2026-08-23.
Power System Ii — Other Year Papers
AKTU Power System Ii PYQs from other sessions
More B.Tech Semester 6 (2024-25) Papers
Other subjects from same semester and session
CMOS Digital Design Techniques2024-25Special Electrical Machines2024-25Augmented Virtual Reality2024-25Software Engineering2024-25River Engineering2024-25Data Compression2024-25Repair And Rehabilitation Of Structures2024-25Idea To Business Model2024-25
View all B.Tech Semester 6 2024-25 papers →Syllabus & More PYQs
Paper solve karne se pehle unit-wise syllabus dekh lo